  1.                          SECTION 08565
  2.  
  3.                       VINYL (PVC) WINDOWS
  4. NOTE ** ALSIDE Window Systems vinyl windows, patio doors,
  5.         and specialty windows.
  6. NOTE **
  7. NOTE ** This section is based on products manufactured by:
  8. NOTE **     ALSIDE Window Systems
  9. NOTE **     P.O. Box 2010 Akron OH 44309
  10. NOTE **     Tel:  (800) 257-4335
  11. NOTE **     Fax:  (330) 922-5387
  12. NOTE **
  13. NOTE ** ALSIDE Window Systems offer a full selection of
  14.         vinyl windows, patio doors, and specialty windows.
  15. NOTE **
  16. NOTE ** SECTION 08565 - VINYL (PVC) WINDOWS, Copyright
  17.         1998, The Architect's Catalog, Inc.
  18.  
  19. PART 1  GENERAL
  20.  
  21. 1.1 SECTION INCLUDES
  22.  
  23.     A.  Single Hung Window Units.
  24.  
  25.     B.  Double Hung Window Units.
  26.  
  27.     C.  Horizontal Sliding Window Units.
  28.  
  29.     D.  Horizontal Sliding Patio Door Units.
  30.  
  31.     E.  Casement Window Units.
  32.  
  33. 1.2 RELATED SECTIONS
  34. NOTE ** Delete any sections below not relevant to this
  35.         project; add others as required.
  36.  
  37.     A.  Section 05400 - Cold Formed Metal Framing.
  38.  
  39.     B.  Section 06100 - Rough Carpentry.
  40.  
  41.     C.  Section 07900 - Joint Sealers.
  42.  
  43.     D.  Section 09100 - Metal Support Systems.
  44.  
  45. 1.3 REFERENCES
  46. NOTE ** Delete any references below not relevant to this
  47.         project; add others as required.
  48.  
  49.     A.  AAMA 101 - Voluntary Standard for Aluminum and Poly
  50.         (Vinyl Chloride) (PVC) Prime Windows and Glass Doors.
  51.  
  52.     B.  NFRC 100 - Thermal Properties; National Fenestration
  53.         Rating Council.
  54.  
  55.     C.  ASTM D 3656 - Standard Specification for Insect Screening
  56.         and Louver Cloth Woven from Vinyl-Coated Glass Fiber
  57.         Yarn.
  58.  
  59.     D.  ASTM D 3678 - Standard Specification for Rigid Poly
  60.         (Vinyl Chloride) (PVC) Interior Profile Extrusions.
  61.  
  62.     E.  ASTM D 4028 - Standard Specification for Solar Screening
  63.         Woven from Vinyl-Coated Fiber Glass Yarn.
  64.  
  65.     F.  ASTM D 4099 - Standard Specification for Poly (Vinyl
  66.         Chloride) (PVC) Prime Windows/Sliding Glass Doors.
  67.  
  68.     G.  ASTM E 774 - Standard Specification for Sealed Insulating
  69.         Glass.
  70.  
  71.     H.  IGCC - Classification of Insulating Glass Units;
  72.         Insulated Glass Certification Council.
  73.  
  74. 1.4 SUBMITTALS
  75.  
  76.     A.  Submit under provisions of Section 01300.
  77.  
  78.     B.  Product Data:  Manufacturer's standard details and
  79.         catalog data demonstrating compliance with referenced
  80.         standards; include manufacturer's standard installation
  81.         instructions.
  82.  
  83.     C.  Drawings:  Manufacturer's product drawings showing
  84.         details of fabrication, hardware, weatherstripping,
  85.         fasteners, screens, glazing, accessories, and related
  86.         items.
  87.  
  88.     D.  Verification Samples:  Operating sample of each window
  89.         type specified illustrating fabrication, hardware,
  90.         glazing, screen, and finish.
  91.  
  92.     E.  Test Reports:  For each window type specified, furnish
  93.         test reports from accredited independent testing
  94.         laboratory certifying that identical or larger window
  95.         units meet requirements specified for air infiltration,
  96.         water penetration and structural performance by ASTM D
  97.         4099 or AAMA 101, for thermal performance by NFRC, and
  98.         for seal integrity of insulating glass units by IGCC.
  99.  
  100.     F.  Closeout Submittals:  Warranty documents, properly
  101.         executed.
  102.  
  103. 1.5 QUALITY ASSURANCE
  104.  
  105.     A.  Manufacturer Qualifications:  Minimum ten (10) years
  106.         experience producing vinyl (PVC) windows.
  107.  
  108. 1.6 DELIVERY, STORAGE AND HANDLING
  109.  
  110.     A.  Deliver windows to project site in undamaged condition;
  111.         handle windows to prevent damage to components and to
  112.         finishes.
  113.  
  114.     B.  Store windows out of contact with ground; protect windows
  115.         from weather and construction traffic in well-ventilated
  116.         area.
  117.  
  118. 1.7 WARRANTY
  119.  
  120.     A.  Furnish manufacturer's standard warranty against
  121.         deficiencies in materials or fabrication.
  122.  
  123.  
  124. PART 2  PRODUCTS
  125.  
  126. 2.1 MANUFACTURERS
  127.  
  128.     A.  Acceptable Manufacturer:  ALSIDE Window Systems;, P.O.
  129.         Box 2010 Akron, OH 44309; ASD. Tel: (800) 257-4335,  Fax:
  130.         (330) 922-5387.
  131.  
  132.     B.  Substitutions:  Not permitted.
  133. NOTE ** Delete the following Article if no single-hung
  134.         window units required.
  135.  
  136. 2.2 SINGLE HUNG WINDOW UNITS
  137. NOTE ** Retain the following paragraph if specifying ALSIDE
  138.         0500 single-hung window units.
  139.  
  140.     A.  Acceptable Product:  ALSIDE MODEL 0500.
  141.         1.  Grade:  ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
  142.             48-inch wide by 72-inch high window unit; exceeding
  143.             grade requirements as follows:
  144.             a.  Water test pressure:  4.5 pounds per square foot.
  145.             b.  Air infiltration:  0.15 cubic feet per minute per
  146.                 linear foot at 25 miles per hour.
  147. NOTE ** Delete one of the following two sub-paragraphs;
  148.         first is for standard glazing, second is for low-e
  149.         glazing with argon gas fill.  Consult with
  150.         manufacturer for thermal performance data if
  151.         optional obscure or tinted glazing is specified.
  152.         2.  Thermal performance, in accordance with NFRC 100, for
  153.             48-inch wide by 72-inch high window unit:  U-Value
  154.             0.50.
  155.         3.  Thermal performance, in accordance with NFRC 100, for
  156.             48-inch wide by 72-inch high window unit:  U-Value
  157.             0.33.
  158. NOTE ** Delete one of the following two sub-paragraphs to
  159.         specify glazing type required; first is for
  160.         standard glazing, second is for low-e glazing with
  161.         argon gas fill.  Obscure glazing and tinted glazing
  162.         are options; consult with manufacturer.
  163.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  164.             unit thickness, with DSB glass.
  165.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  166.             inch unit thickness, with DSB glass and argon gas
  167.             fill.
  168.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  169.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  170.             Spacer System.
  171.         7.  Frame:  PVC extrusions, overlapping butt-joint
  172.             construction, joined with screws into integral screw
  173.             ports; sloped sill for positive drainage.
  174.         8.  Sash:  PVC extrusions, tilt-in operation of lower
  175.             sash for cleaning, with spiral balances, integral
  176.             double walled lift rail for added strength,
  177.             interlocking with fixed meeting rail of main frame,
  178.             and cam-type sweep locks and keepers.
  179.         9.  Insect screening:  Roll-formed or extruded aluminum
  180.             channel frames, with 18 by 16 fiberglass mesh secured
  181.             with continuous vinyl gasket, removable for screen
  182.             replacement.
  183. NOTE ** Delete the following paragraph if muntins are not
  184.         required.
  185.         10. Muntins:  Colonial grid installed between outer and
  186.             inner glass panes during fabrication of insulating
  187.             glass units.
  188. NOTE ** Retain the following paragraph if specifying ALSIDE
  189.         0100 single-hung new construction window units in
  190.         Grade 20.
  191.  
  192.     B.  Acceptable Product:  ALSIDE MODEL 0100.
  193.         1.  Grade:  ASTM D 4099 Grade 20, AAMA 101 Grade R20, for
  194.             48-inch wide by 72-inch high window unit; exceeding
  195.             grade requirements as follows:
  196.             a.  Water test pressure:  3.0 pounds per square foot.
  197.             b.  Air infiltration:  0.10 cubic feet per minute per
  198.                 linear foot at 25 miles per hour.
  199.             c.  Test pressure sustained without damage:  30
  200.                 pounds per square foot.
  201. NOTE ** Delete one of the following two sub-paragraphs;
  202.         first is for standard glazing, second is for low-e
  203.         glazing with argon gas fill.  Consult with
  204.         manufacturer for thermal performance data if
  205.         optional obscure or tinted glazing is specified.
  206.         2.  Thermal performance, in accordance with NFRC 100, for
  207.             48-inch wide by 72-inch high window unit:  U-Value
  208.             0.50.
  209.         3.  Thermal performance, in accordance with NFRC 100, for
  210.             48-inch wide by 72-inch high window unit:  U-Value
  211.             0.31.
  212. NOTE ** Delete one of the following two sub-paragraphs to
  213.         specify glazing type required; first is for
  214.         standard glazing, second is for low-e glazing with
  215.         argon gas fill.  Obscure glazing and tinted glazing
  216.         are options; consult with manufacturer.
  217.         4.  Glazing:  Sealed insulating glass unit, 3/4 inch unit
  218.             thickness, with SSB glass.
  219.         5.  Glazing:  Low-e sealed insulating glass unit, 3/4
  220.             inch unit thickness, with SSB glass and argon gas
  221.             fill.
  222.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  223.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  224.             Spacer System.
  225.         7.  Frame:  PVC extrusions, fusion-welded construction,
  226.             mitered corners.
  227.         8.  Sash:  Narrow-line fusion-welded PVC extrusions,
  228.             mitered corners, tilt-in operation of lower sash for
  229.             cleaning, with spiral balances, integral lift rail
  230.             for added strength, interlocking with fixed meeting
  231.             rail of main frame, and cam-type sweep locks and
  232.             keepers.
  233.         9.  Nailing fin:  Extruded PVC, 1-1/8 inches wide, four
  234.             sides.
  235.         10. Insect screening:  Roll-formed or extruded aluminum
  236.             channel frames, with 18 by 16 fiberglass mesh secured
  237.             with continuous vinyl gasket, removable for screen
  238.             replacement.
  239. NOTE ** Delete the following paragraph if muntins are not
  240.         required.
  241.         11. Muntins:  Colonial grid installed between outer and
  242.             inner glass panes during fabrication of insulating
  243.             glass units.
  244. NOTE ** Delete the following Article if no double-hung
  245.         window units required.
  246.  
  247. 2.3 DOUBLE HUNG WINDOW UNITS
  248. NOTE ** Retain the following paragraph if specifying ALSIDE
  249.         0901 double-hung window units.
  250.  
  251.     A.  Acceptable Product:  ALSIDE MODEL 0901.
  252.         1.  Grade:  ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
  253.             48-inch wide by 72-inch high window unit; exceeding
  254.             grade requirements as follows:
  255.             a.  Water test pressure:  5.0 pounds per square foot.
  256.             b.  Air infiltration:  0.16 cubic feet per minute per
  257.                 linear foot at 25 miles per hour.
  258. NOTE ** Delete one of the following two sub-paragraphs;
  259.         first is for standard glazing, second is for low-e
  260.         glazing with argon gas fill.  Consult with
  261.         manufacturer for thermal performance data if
  262.         optional obscure or tinted glazing is specified.
  263.         2.  Thermal performance, in accordance with NFRC 100, for
  264.             48-inch wide by 72-inch high window unit:  U-Value
  265.             0.50.
  266.         3.  Thermal performance, in accordance with NFRC 100, for
  267.             48-inch wide by 72-inch high window unit:  U-Value
  268.             0.34.
  269. NOTE ** Delete one of the following two sub-paragraphs to
  270.         specify glazing type required; first is for
  271.         standard glazing, second is for low-e glazing with
  272.         argon gas fill.  Obscure glazing and tinted glazing
  273.         are options; consult with manufacturer.
  274.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  275.             unit thickness, with DSB glass.
  276.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  277.             inch unit thickness, with DSB glass and argon gas
  278.             fill.
  279.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  280.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  281.             Spacer System.
  282.         7.  Frame:  PVC extrusions, telescoping butt-joint
  283.             construction reinforced at corners, joined with
  284.             screws into integral screw ports; sloped sill for
  285.             positive drainage.
  286.         8.  Sash:  PVC extrusions, aluminum reinforced horizontal
  287.             members for window units over 28-7/8 inches wide,
  288.             tilt-in operation of upper and lower sash for
  289.             cleaning, with field-adjustable spiral balances,
  290.             integral double walled lift rail for added strength,
  291.             interlocking meeting rails and cam-type sweep locks
  292.             and keepers.
  293.         9.  Insect screening:  Roll-formed or extruded aluminum
  294.             channel frames, with 18 by 16 fiberglass mesh secured
  295.             with continuous vinyl gasket, removable for screen
  296.             replacement.
  297. NOTE ** Delete the following paragraph if muntins are not
  298.         required.
  299.         10. Muntins:  Colonial grid installed between outer and
  300.             inner glass panes during fabrication of insulating
  301.             glass units.
  302. NOTE ** Retain the following paragraph if specifying ALSIDE
  303.         0601 double-hung window units in standard Grade 45.
  304.  
  305.     B.  Acceptable Product:  ALSIDE MODEL 0601.
  306.         1.  Grade:  ASTM D 4099 Grade 45, AAMA 101 Grade R45, for
  307.             47-inch wide by 60-inch high window unit; exceeding
  308.             grade requirements as follows:
  309.             a.  Water test pressure:  6.0 pounds per square foot.
  310.             b.  Air infiltration:  0.13 cubic feet per minute per
  311.                 linear foot at 25 miles per hour.
  312. NOTE ** Delete one of the following two sub-paragraphs;
  313.         first is for standard glazing, second is for low-e
  314.         glazing with argon gas fill.  Consult with
  315.         manufacturer for thermal performance data if
  316.         optional obscure or tinted glazing is specified.
  317.         2.  Thermal performance, in accordance with NFRC 100, for
  318.             48-inch wide by 72-inch high window unit:  U-Value
  319.             0.47.
  320.         3.  Thermal performance, in accordance with NFRC 100, for
  321.             48-inch wide by 72-inch high window unit:  U-Value
  322.             0.32.
  323. NOTE ** Delete one of the following two sub-paragraphs to
  324.         specify glazing type required; first is for
  325.         standard glazing, second is for low-e glazing with
  326.         argon gas fill.  Obscure glazing and tinted glazing
  327.         are options; consult with manufacturer.
  328.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  329.             unit thickness, with DSB glass.
  330.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  331.             inch unit thickness, with DSB glass and argon gas
  332.             fill.
  333.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  334.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  335.             Spacer System.
  336.         7.  Frame:  PVC extrusions, fusion-welded construction,
  337.             mitered corners; concealed screen track.
  338.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  339.             construction, mitered corners, tilt-in operation of
  340.             upper and lower sash for cleaning, with field-
  341.             adjustable spiral balances, double lift rail on
  342.             bottom sash, interlocking meeting rails, and cam-type
  343.             sweep locks and keepers.
  344.         9.  Insect screening:  Roll-formed or extruded aluminum
  345.             channel frames, with 18 by 16 fiberglass mesh secured
  346.             with continuous vinyl gasket, removable for screen
  347.             replacement.
  348. NOTE ** Delete the following paragraph if muntins are not
  349.         required.
  350.         10. Muntins:  Colonial grid installed between outer and
  351.             inner glass panes during fabrication of insulating
  352.             glass units.
  353. NOTE ** Retain the following paragraph if specifying ALSIDE
  354.         3001 double-hung window units.
  355.  
  356.     C.  Acceptable Product:  ALSIDE MODEL 3001.
  357.         1.  Grade:  ASTM D 4099 Grade 45, AAMA 101 Grade R45, for
  358.             48-inch wide by 72-inch high window unit; exceeding
  359.             grade requirements as follows:
  360.             a.  Water test pressure:  4.5 pounds per square foot.
  361.             b.  Air infiltration:  0.19 cubic feet per minute per
  362.                 linear foot at 25 miles per hour.
  363. NOTE ** Delete one of the following two sub-paragraphs;
  364.         first is for standard glazing, second is for low-e
  365.         glazing with argon gas fill.  Consult with
  366.         manufacturer for thermal performance data if
  367.         optional obscure or tinted glazing is specified.
  368.         2.  Thermal performance, in accordance with NFRC 100, for
  369.             48-inch wide by 72-inch high window unit:  U-Value
  370.             0.49.
  371.         3.  Thermal performance, in accordance with NFRC 100, for
  372.             48-inch wide by 72-inch high window unit:  U-Value
  373.             0.34.
  374. NOTE ** Delete one of the following two sub-paragraphs to
  375.         specify glazing type required; first is for
  376.         standard glazing, second is for low-e glazing with
  377.         argon gas fill.  Obscure glazing and tinted glazing
  378.         are options; consult with manufacturer.
  379.         4.  Glazing:  Sealed insulating glass unit, 15/16 inch
  380.             unit thickness, with DSB glass.
  381.         5.  Glazing:  Low-e sealed insulating glass unit, 15/16
  382.             inch unit thickness, with DSB glass and argon gas
  383.             fill.
  384.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  385.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  386.             Spacer System.
  387.         7.  Frame:  PVC extrusions, butt-joint construction,
  388.             sloped hospital sill for positive drainage.
  389.         8.  Sash:  PVC extrusions, mitered corners joined with 4
  390.             screws per corner into heavy duty corner gussets;
  391.             tilt-in operation of upper and lower sash for
  392.             cleaning, with field-adjustable spiral balances;
  393.             integral double walled lift rail for added strength,
  394.             interlocking meeting rails on top and bottom sash,
  395.             and cam-type sweep locks and keepers.
  396.         9.  Insect screening:  Roll-formed or extruded aluminum
  397.             channel frames, with 18 by 16 fiberglass mesh secured
  398.             with continuous vinyl gasket, removable for screen
  399.             replacement.
  400. NOTE ** Delete options specified in the following two
  401.         paragraphs if not required.
  402.         10. Reinforcement:  Steel reinforced frame and/or sash.
  403.         11. Muntins:  Colonial grid installed between outer and
  404.             inner glass panes during fabrication of insulating
  405.             glass units.
  406. NOTE ** Retain the following paragraph if specifying ALSIDE
  407.         O201 double-hung window units.
  408.  
  409.     D.  Acceptable Product:  ALSIDE MODEL O201.
  410.         1.  Grade:  ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
  411.             48-inch wide by 60-inch high window unit; exceeding
  412.             grade requirements as follows:
  413.             a.  Water test pressure:  4.5 pounds per square foot.
  414.             b.  Air infiltration:  0.15 cubic feet per minute per
  415.                 linear foot at 25 miles per hour.
  416. NOTE ** Delete one of the following two sub-paragraphs;
  417.         first is for standard glazing, second is for low-e
  418.         glazing with argon gas fill.  Consult with
  419.         manufacturer for thermal performance data if
  420.         optional obscure or tinted glazing is specified.
  421.         2.  Thermal performance, in accordance with NFRC 100, for
  422.             48-inch wide by 72-inch high window unit:  U-Value
  423.             0.51.
  424.         3.  Thermal performance, in accordance with NFRC 100, for
  425.             48-inch wide by 72-inch high window unit:  U-Value
  426.             0.36.
  427. NOTE ** Delete one of the following two sub-paragraphs to
  428.         specify glazing type required; first is for
  429.         standard glazing, second is for low-e glazing with
  430.         argon gas fill.  Obscure glazing and tinted glazing
  431.         are options; consult with manufacturer.
  432.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  433.             unit thickness, with DSB glass.
  434.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  435.             inch unit thickness, with DSB glass and argon gas
  436.             fill.
  437.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  438.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  439.             Spacer System.
  440.         7.  Frame:  PVC extrusions, fusion-welded construction,
  441.             mitered corners; sloped sill for positive drainage.
  442.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  443.             construction, mitered corners, tilt-in operation of
  444.             upper and lower sash for cleaning, with field-
  445.             adjustable spiral balances, interlocking meeting
  446.             rails, and cam-type sweep locks and keepers.
  447.         9.  Insect screening:  Roll-formed or extruded aluminum
  448.             channel frames, with 18 by 16 fiberglass mesh secured
  449.             with continuous vinyl gasket, removable for screen
  450.             replacement.
  451. NOTE ** Delete the following paragraph if muntins are not
  452.         required.
  453.         10. Muntins:  Colonial grid installed between outer and
  454.             inner glass panes during fabrication of insulating
  455.             glass units.
  456. NOTE ** Retain the following paragraph if specifying ALSIDE
  457.         0401 double-hung window units.
  458.  
  459.     E.  Acceptable Product:  ALSIDE MODEL 0401.
  460.         1.  Grade:  ASTM D 4099 Grade 35, AAMA 101 Grade R35, for
  461.             36-inch wide by 60-inch high window unit; exceeding
  462.             grade requirements as follows:
  463.             a.  Water test pressure:  4.50 pounds per square
  464.                 foot.
  465.             b.  Air infiltration:  0.15 cubic feet per minute per
  466.                 linear foot at 25 miles per hour.
  467. NOTE ** Delete one of the following two sub-paragraphs;
  468.         first is for standard glazing, second is for low-e
  469.         glazing with argon gas fill.  Consult with
  470.         manufacturer for thermal performance data if
  471.         optional obscure or tinted glazing is specified.
  472.         2.  Thermal performance, in accordance with NFRC 100, for
  473.             48-inch wide by 72-inch high window unit:  U-Value
  474.             0.49.
  475.         3.  Thermal performance, in accordance with NFRC 100, for
  476.             48-inch wide by 72-inch high window unit:  U-Value
  477.             0.33.
  478. NOTE ** Delete one of the following two sub-paragraphs to
  479.         specify glazing type required; first is for
  480.         standard glazing, second is for low-e glazing with
  481.         argon gas fill.  Obscure glazing and tinted glazing
  482.         are options; consult with manufacturer.
  483.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  484.             unit thickness, with DSB glass.
  485.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  486.             inch unit thickness, with DSB glass and argon gas
  487.             fill.
  488.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  489.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  490.             Spacer System.
  491.         7.  Frame:  PVC extrusions, telescoping butt-joint
  492.             construction reinforced at corners, joined with
  493.             screws into integral screw ports; sloped sill for
  494.             positive drainage.
  495.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  496.             construction, mitered corners, tilt-in operation of
  497.             upper and lower sash for cleaning, with field-
  498.             adjustable spiral balances, double lift rail on
  499.             bottom sash, interlocking meeting rails, and cam-type
  500.             sweep locks and keepers.
  501.         9.  Insect screening:  Roll-formed or extruded aluminum
  502.             channel frames, with 18 by 16 fiberglass mesh secured
  503.             with continuous vinyl gasket, removable for screen
  504.             replacement.
  505. NOTE ** Delete the following paragraph if muntins are not
  506.         required.
  507.         10. Muntins:  Colonial grid installed between outer and
  508.             inner glass panes during fabrication of insulating
  509.             glass units.
  510.  
  511.     F.  Acceptable Product:  ALSIDE MODEL 0301.
  512.         1.  Grade:  ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
  513.             48-inch wide by 60-inch high window unit; exceeding
  514.             grade requirements as follows:
  515.             a.  Water test pressure:  4.5 pounds per square foot.
  516.             b.  Air infiltration:  0.15 cubic feet per minute per
  517.                 linear foot at 25 miles per hour.
  518. NOTE ** Delete one of the following two sub-paragraphs;
  519.         first is for standard glazing, second is for low-e
  520.         glazing with argon gas fill.  Consult with
  521.         manufacturer for thermal performance data if
  522.         optional obscure or tinted glazing is specified.
  523.         2.  Thermal performance, in accordance with NFRC 100, for
  524.             48-inch wide by 72-inch high window unit:  U-Value
  525.             0.51.
  526.         3.  Thermal performance, in accordance with NFRC 100, for
  527.             48-inch wide by 72-inch high window unit:  U-Value
  528.             0.36.
  529. NOTE ** Delete one of the following two sub-paragraphs to
  530.         specify glazing type required; first is for
  531.         standard glazing, second is for low-e glazing with
  532.         argon gas fill.  Obscure glazing and tinted glazing
  533.         are options; consult with manufacturer.
  534.         4.  Glazing:  Sealed insulating glass unit, 3/4 inch unit
  535.             thickness, with SSB glass.
  536.         5.  Glazing:  Low-e sealed insulating glass unit, 3/4
  537.             inch unit thickness, with SSB glass and argon gas
  538.             fill.
  539.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  540.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  541.             Spacer System.
  542.         7.  Frame:  PVC extrusions, fusion-welded construction,
  543.             mitered corners; sloped sill for positive drainage,
  544.             integral J-channel.
  545.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  546.             construction, mitered corners, tilt-in operation of
  547.             upper and lower sash for cleaning, with field-
  548.             adjustable spiral balances, interlocking meeting
  549.             rails, and cam-type sweep locks and keepers.
  550.         9.  Nailing fin:  Extruded PVC, four sides, 1.75 wide.
  551.         10. Insect screening:  Roll-formed or extruded aluminum
  552.             channel frames, with 18 by 16 fiberglass mesh secured
  553.             with continuous vinyl gasket, removable for screen
  554.             replacement.
  555. NOTE ** Delete the following paragraph if muntins are not
  556.         required.
  557.         11. Muntins:  Colonial grid installed between outer and
  558.             inner glass panes during fabrication of insulating
  559.             glass units.
  560. NOTE ** Delete the following Article if no horizontal-
  561.         sliding window units required.
  562.  
  563. 2.4 HORIZONTAL SLIDING WINDOW UNITS
  564. NOTE ** Retain the following paragraph if specifying ALSIDE
  565.         0902 horizontal-sliding window units.
  566.  
  567.     A.  Acceptable Product:  ALSIDE MODEL 0902.
  568.         1.  Grade:  ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
  569.             72-inch wide by 48-inch high window unit; exceeding
  570.             grade requirements as follows:
  571.             a.  Water test pressure:  4.5 pounds per square foot.
  572.             b.  Air infiltration:  0.20 cubic feet per minute per
  573.                 linear foot at 25 miles per hour.
  574. NOTE ** Delete one of the following two sub-paragraphs;
  575.         first is for standard glazing, second is for low-e
  576.         glazing with argon gas fill.  Consult with
  577.         manufacturer for thermal performance data if
  578.         optional obscure or tinted glazing is specified.
  579.         2.  Thermal performance, in accordance with NFRC 100, for
  580.             72-inch wide by 48-inch high window unit:  U-Value
  581.             0.50.
  582.         3.  Thermal performance, in accordance with NFRC 100, for
  583.             72-inch wide by 48-inch high window unit:  U-Value
  584.             0.34.
  585. NOTE ** Delete one of the following two sub-paragraphs to
  586.         specify glazing type required; first is for
  587.         standard glazing, second is for low-e glazing with
  588.         argon gas fill.  Obscure glazing and tinted glazing
  589.         are options; consult with manufacturer.
  590.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  591.             unit thickness, with DSB glass.
  592.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  593.             inch unit thickness, with DSB glass and argon gas
  594.             fill.
  595.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  596.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  597.             Spacer System.
  598.         7.  Frame:  PVC extrusions, butt-joint construction at
  599.             corners, joined with screws into integral screw
  600.             ports; multi-chambered weep system with wind-blocking
  601.             covers.
  602.         8.  Sash:  PVC extrusions, aluminum-reinforced vertical
  603.             members for window units over 29-1/2 inches high,
  604.             lift-out operation of both operable sash units, with
  605.             nylon-encased metal dual-roller system, full-
  606.             interlocking meeting rails, full sash capture at
  607.             jamb, sash vent lock, theft-deterrent blocks, and cam-
  608.             type sweep locks and keepers.
  609.         9.  Insect screening:  Roll-formed or extruded aluminum
  610.             channel frames, with 18 by 16 fiberglass mesh secured
  611.             with continuous vinyl gasket, removable for screen
  612.             replacement.
  613. NOTE ** Delete the following paragraph if muntins are not
  614.         required.
  615.         10. Muntins:  Colonial grid installed between outer and
  616.             inner glass panes during fabrication of insulating
  617.             glass units.
  618. NOTE ** Retain the following paragraph if specifying ALSIDE
  619.         0602 horizontal-sliding window units.
  620.  
  621.     B.  Acceptable Product:  ALSIDE MODEL 0602.
  622.         1.  Grade:  ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
  623.             72-inch wide by 51-inch high window unit; exceeding
  624.             grade requirements as follows:
  625.             a.  Water test pressure:  6.5 pounds per square foot.
  626.             b.  Air infiltration:  0.20 cubic feet per minute per
  627.                 linear foot at 25 miles per hour.
  628. NOTE ** Delete one of the following two sub-paragraphs;
  629.         first is for standard glazing, second is for low-e
  630.         glazing with argon gas fill.  Consult with
  631.         manufacturer for thermal performance data if
  632.         optional obscure or tinted glazing is specified.
  633.         2.  Thermal performance, in accordance with NFRC 100, for
  634.             72-inch wide by 48-inch high window unit:  U-Value
  635.             0.47.
  636.         3.  Thermal performance, in accordance with NFRC 100, for
  637.             72-inch wide by 48-inch high window unit:  U-Value
  638.             0.31.
  639. NOTE ** Delete one of the following two sub-paragraphs to
  640.         specify glazing type required; first is for
  641.         standard glazing, second is for low-e glazing with
  642.         argon gas fill.  Obscure glazing and tinted glazing
  643.         are options; consult with manufacturer.
  644.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  645.             unit thickness, with DSB glass.
  646.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  647.             inch unit thickness, with DSB glass and argon gas
  648.             fill.
  649.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  650.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  651.             Spacer System.
  652.         7.  Frame:  PVC extrusions, fusion-welded construction,
  653.             mitered corners; step sill for positive drainage,
  654.             concealed screen track.
  655.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  656.             construction, mitered corners, lift-out operation of
  657.             both operable sash units, with nylon-encased metal
  658.             dual-roller system, full-interlocking meeting rails,
  659.             full sash capture at jamb, sash vent lock, theft-
  660.             deterrent blocks, cam-type locks with keepers.
  661.         9.  Insect screening:  Roll-formed or extruded aluminum
  662.             channel frames, with 18 by 16 fiberglass mesh secured
  663.             with continuous vinyl gasket, removable for screen
  664.             replacement.
  665. NOTE ** Delete the following paragraph if muntins are not
  666.         required.
  667.         10. Muntins:  Colonial grid installed between outer and
  668.             inner glass panes during fabrication of insulating
  669.             glass units.
  670. NOTE ** Retain the following paragraph if specifying ALSIDE
  671.         3002 horizontal-sliding window units.
  672.  
  673.     C.  Acceptable Product:  ALSIDE MODEL 3002.
  674.         1.  Grade:  ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
  675.             72-inch wide by 50-inch high window unit; exceeding
  676.             grade requirements as follows:
  677.             a.  Water test pressure:  5.0 pounds per square foot.
  678.             b.  Air infiltration:  0.16 cubic feet per minute per
  679.                 linear foot at 25 miles per hour.
  680. NOTE ** Delete one of the following two sub-paragraphs;
  681.         first is for standard glazing, second is for low-e
  682.         glazing with argon gas fill.  Consult with
  683.         manufacturer for thermal performance data if
  684.         optional obscure or tinted glazing is specified.
  685.         2.  Thermal performance, in accordance with NFRC 100, for
  686.             72-inch wide by 48-inch high window unit:  U-Value
  687.             0.49.
  688.         3.  Thermal performance, in accordance with NFRC 100, for
  689.             72-inch wide by 48-inch high window unit:  U-Value
  690.             0.35.
  691. NOTE ** Delete one of the following two sub-paragraphs to
  692.         specify glazing type required; first is for
  693.         standard glazing, second is for low-e glazing with
  694.         argon gas fill.  Obscure glazing and tinted glazing
  695.         are options; consult with manufacturer.
  696.         4.  Glazing:  Sealed insulating glass unit, 15/16 inch
  697.             unit thickness, with DSB glass.
  698.         5.  Glazing:  Low-e sealed insulating glass unit, 15/16
  699.             inch unit thickness, with DSB glass and argon gas
  700.             fill.
  701.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  702.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  703.             Spacer System.
  704.         7.  Frame:  PVC extrusions, fusion-welded construction,
  705.             mitered corners.
  706.         8.  Sash:  PVC extrusions, mitered corners with heavy
  707.             duty corner gussets secured by four (4) screw
  708.             fasteners each corner, lift-out operation of both
  709.             operable sash units, with nylon-encased metal dual-
  710.             roller system, full-interlocking meeting rails, full
  711.             sash capture at jamb, sash vent lock, theft-deterrent
  712.             blocks, dual chrome-plated cam-type locks with
  713.             stainless steel keepers.
  714.         9.  Insect screening:  Roll-formed or extruded aluminum
  715.             channel frames, with 18 by 16 fiberglass mesh secured
  716.             with continuous vinyl gasket, removable for screen
  717.             replacement.
  718. NOTE ** Delete the following paragraph if muntins are not
  719.         required.
  720.         10. Muntins:  Colonial grid installed between outer and
  721.             inner glass panes during fabrication of insulating
  722.             glass units.
  723. NOTE ** Retain the following paragraph if specifying ALSIDE
  724.         0102 horizontal-sliding window units.
  725.  
  726.     D.  Acceptable Product:  ALSIDE MODEL 0102.
  727.         1.  Grade:  ASTM D 4099 Grade 25, AAMA 101 Grade R25, for
  728.             72-inch wide by 48-inch high window unit; exceeding
  729.             grade requirements as follows:
  730.             a.  Water test pressure:  5.25 pounds per square
  731.                 foot.
  732.             b.  Air infiltration:  0.10 cubic feet per minute per
  733.                 linear foot at 25 miles per hour.
  734. NOTE ** Delete one of the following two sub-paragraphs;
  735.         first is for standard glazing, second is for low-e
  736.         glazing with argon gas fill.  Consult with
  737.         manufacturer for thermal performance data if
  738.         optional obscure or tinted glazing is specified.
  739.         2.  Thermal performance, in accordance with NFRC 100, for
  740.             72-inch wide by 48-inch high window unit:  U-Value
  741.             0.50.
  742.         3.  Thermal performance, in accordance with NFRC 100, for
  743.             72-inch wide by 48-inch high window unit:  U-Value
  744.             0.31.
  745. NOTE ** Delete one of the following two sub-paragraphs to
  746.         specify glazing type required; first is for
  747.         standard glazing, second is for low-e glazing with
  748.         argon gas fill.  Obscure glazing and tinted glazing
  749.         are options; consult with manufacturer.
  750.         4.  Glazing:  Sealed insulating glass unit, 3/4 inch unit
  751.             thickness, with SSB glass.
  752.         5.  Glazing:  Low-e sealed insulating glass unit, 3/4
  753.             inch unit thickness, with SSB glass and argon gas
  754.             fill.
  755.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  756.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  757.             Spacer System.
  758.         7.  Frame:  PVC extrusions, fusion-welded construction,
  759.             mitered corners; weeps in sill for positive drainage,
  760.             extruded PVC nailing fin four (4) sides.
  761.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  762.             construction, mitered corners, lift-out operation of
  763.             operable sash unit, with full-interlocking meeting
  764.             rail, full sash capture at jamb, cam-type locks with
  765.             keepers.
  766.         9.  Insect screening:  Roll-formed or extruded aluminum
  767.             channel frames, with 18 by 16 fiberglass mesh secured
  768.             with continuous vinyl gasket, removable for screen
  769.             replacement.
  770. NOTE ** Delete the following paragraph if muntins are not
  771.         required.
  772.         10. Muntins:  Colonial grid installed between outer and
  773.             inner glass panes during fabrication of insulating
  774.             glass units.
  775. NOTE ** Retain the following paragraph if specifying ALSIDE
  776.         O202 horizontal-sliding window units.
  777.  
  778.     E.  Acceptable Product:  ALSIDE MODEL O202.
  779.         1.  Grade:  ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
  780.             60-inch wide by 36-inch high window unit; exceeding
  781.             grade requirements as follows:
  782.             a.  Water test pressure:  6.0 pounds per square foot.
  783.             b.  Air infiltration:  0.12 cubic feet per minute per
  784.                 linear foot at 25 miles per hour.
  785. NOTE ** Delete one of the following two sub-paragraphs;
  786.         first is for standard glazing, second is for low-e
  787.         glazing with argon gas fill.  Consult with
  788.         manufacturer for thermal performance data if
  789.         optional obscure or tinted glazing is specified.
  790.         2.  Thermal performance, in accordance with NFRC 100, for
  791.             72-inch wide by 48-inch high window unit:  U-Value
  792.             0.49.
  793.         3.  Thermal performance, in accordance with NFRC 100, for
  794.             72-inch wide by 48-inch high window unit:  U-Value
  795.             0.35.
  796. NOTE ** Delete one of the following two sub-paragraphs to
  797.         specify glazing type required; first is for
  798.         standard glazing, second is for low-e glazing with
  799.         argon gas fill.  Obscure glazing and tinted glazing
  800.         are options; consult with manufacturer.
  801.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  802.             unit thickness, with DSB glass.
  803.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  804.             inch unit thickness, with DSB glass and argon gas
  805.             fill.
  806.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  807.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  808.             Spacer System.
  809.         7.  Frame:  PVC extrusions, fusion-welded construction,
  810.             mitered corners; weeps in sill for positive drainage.
  811.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  812.             construction, lift-out operation of both operable
  813.             sash units, with nylon-encased metal dual-roller
  814.             system, full-interlocking meeting rails, full sash
  815.             capture at sill, cam-type locks with keepers.
  816.         9.  Insect screening:  Roll-formed or extruded aluminum
  817.             channel frames, with 18 by 16 fiberglass mesh secured
  818.             with continuous vinyl gasket, removable for screen
  819.             replacement.
  820. NOTE ** Delete the following paragraph if muntins are not
  821.         required.
  822.         10. Muntins:  Colonial grid installed between outer and
  823.             inner glass panes during fabrication of insulating
  824.             glass units.
  825. NOTE ** Retain the following paragraph if specifying ALSIDE
  826.         O402 horizontal-sliding window units.
  827.  
  828.     F.  Acceptable Product:  ALSIDE MODEL O402.
  829.         1.  Grade:  ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
  830.             72-inch wide by 48-inch high window unit; exceeding
  831.             grade requirements as follows:
  832.             a.  Water test pressure:  5.25 pounds per square
  833.                 foot.
  834.             b.  Air infiltration:  0.20 cubic feet per minute per
  835.                 linear foot at 25 miles per hour.
  836. NOTE ** Delete one of the following two sub-paragraphs;
  837.         first is for standard glazing, second is for low-e
  838.         glazing with argon gas fill.  Consult with
  839.         manufacturer for thermal performance data if
  840.         optional obscure or tinted glazing is specified.
  841.         2.  Thermal performance, in accordance with NFRC 100, for
  842.             72-inch wide by 48-inch high window unit:  U-Value
  843.             0.49.
  844.         3.  Thermal performance, in accordance with NFRC 100, for
  845.             72-inch wide by 48-inch high window unit:  U-Value
  846.             0.33.
  847. NOTE ** Delete one of the following two sub-paragraphs to
  848.         specify glazing type required; first is for
  849.         standard glazing, second is for low-e glazing with
  850.         argon gas fill.  Obscure glazing and tinted glazing
  851.         are options; consult with manufacturer.
  852.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  853.             unit thickness, with DSB glass.
  854.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  855.             inch unit thickness, with DSB glass and argon gas
  856.             fill.
  857.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  858.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  859.             Spacer System.
  860.         7.  Frame:  PVC extrusions, butt-joint construction at
  861.             corners, joined with screws into integral screw
  862.             ports; multi-chambered weep system with wind-blocking
  863.             covers.
  864.         8.  Sash:  PVC extrusions, fusion-welded narrow-line
  865.             construction, mitered corners, lift-out operation of
  866.             both operable sash units, with nylon-encased metal
  867.             dual-roller system, full-interlocking meeting rails,
  868.             full sash capture at jamb, cam-type locks with
  869.             keepers.
  870.         9.  Insect screening:  Roll-formed or extruded aluminum
  871.             channel frames, with 18 by 16 fiberglass mesh secured
  872.             with continuous vinyl gasket, removable for screen
  873.             replacement.
  874. NOTE ** Delete the following paragraph if muntins are not
  875.         required.
  876.         10. Muntins:  Colonial grid installed between outer and
  877.             inner glass panes during fabrication of insulating
  878.             glass units.
  879. NOTE ** Delete the following Article if no horizontal-
  880.         sliding patio door units required.
  881.  
  882. 2.5 HORIZONTAL SLIDING PATIO DOOR UNITS
  883. NOTE ** Retain the following paragraph if specifying ALSIDE
  884.         6100 horizontal-sliding patio door units.
  885.  
  886.     A.  Acceptable Product:  ALSIDE MODEL 6100.
  887.         1.  Grade:  ASTM D 4099 Grade 35, AAMA 101 Grade R35, for
  888.             69-inch wide by 79-inch high door unit; exceeding
  889.             grade requirements as follows:
  890.             a.  Water test pressure:  4.5 pounds per square foot.
  891.             b.  Air infiltration:  0.15 cubic feet per minute per
  892.                 linear foot at 25 miles per hour.
  893. NOTE ** Delete one of the following two sub-paragraphs;
  894.         first is for standard glazing, second is for low-e
  895.         glazing with argon gas fill.  Consult with
  896.         manufacturer for thermal performance data if
  897.         optional colonial grooved or tinted glazing is
  898.         specified.
  899.         2.  Thermal performance, in accordance with NFRC 100, for
  900.             72-inch wide by 96-inch high door unit:  U-Value
  901.             0.54.
  902.         3.  Thermal performance, in accordance with NFRC 100, for
  903.             72-inch wide by 96-inch high door unit:  U-Value
  904.             0.39.
  905. NOTE ** Delete one of the following two sub-paragraphs to
  906.         specify glazing type required; first is for
  907.         standard glazing, second is for low-e glazing with
  908.         argon gas fill.  Colonial grooved glazing and
  909.         tinted glazing are options; consult with
  910.         manufacturer.
  911.         4.  Glazing:  Sealed insulating glass unit, 7/8 inch unit
  912.             thickness, with fully-tempered DSB glass.
  913.         5.  Glazing:  Low-e sealed insulating glass unit, 7/8
  914.             inch unit thickness, with fully-tempered DSB glass
  915.             and argon gas fill.
  916.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  917.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  918.             Spacer System.
  919.         7.  Frame:  Vinyl-clad wood, triple-screw butt-joint
  920.             construction; sloped vinyl sill with steel roller
  921.             track.
  922.         8.  Sash:  PVC extrusions, butt-joint construction, steel-
  923.             reinforced vertical members, operable sash unit with
  924.             adjustable dual-roller system, full-interlocking
  925.             meeting rails, full sash capture at jamb, and
  926.             latching hardware with keeper.
  927.         9.  Insect screening:  Roll-formed or extruded aluminum
  928.             channel frames, with 18 by 16 fiberglass mesh secured
  929.             with continuous vinyl gasket, removable for screen
  930.             replacement; four-point adjustable rollers.
  931. NOTE ** Delete the options in the following four paragraphs
  932.         if not required.
  933.         10. Muntins:  Colonial grid installed between outer and
  934.             inner glass panes during fabrication of insulating
  935.             glass units.
  936.         11. Hardware operation:  Keyed lock on exterior side,
  937.             with two (2) keys.
  938.         12. Hardware finish:  Brass.
  939.         13. Vent lock.
  940. NOTE ** Retain the following paragraph if specifying ALSIDE
  941.         2100 horizontal-sliding patio door units.
  942.     B.  Acceptable Product:  ALSIDE MODEL 2100.
  943.         1.  Grade:  ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
  944.             72-inch wide by 80-inch high door unit; exceeding
  945.             grade requirements as follows:
  946.             a.  Water test pressure:  3.75 pounds per square
  947.                 foot.
  948.             b.  Air infiltration:  0.09 cubic feet per minute per
  949.                 linear foot at 25 miles per hour.
  950. NOTE ** Delete one of the following two sub-paragraphs;
  951.         first is for standard glazing, second is for low-e
  952.         glazing with argon gas fill.  Consult with
  953.         manufacturer for thermal performance data if
  954.         optional colonial grooved or tinted glazing is
  955.         specified.
  956.         2.  Thermal performance, in accordance with NFRC 100, for
  957.             72-inch wide by 96-inch high door unit:  U-Value
  958.             0.50.
  959.         3.  Thermal performance, in accordance with NFRC 100, for
  960.             72-inch wide by 96-inch high door unit:  U-Value
  961.             0.34.
  962. NOTE ** Delete one of the following two sub-paragraphs to
  963.         specify glazing type required; first is for
  964.         standard glazing, second is for low-e glazing with
  965.         argon gas fill.  Colonial grooved glazing and
  966.         tinted glazing are options; consult with
  967.         manufacturer.
  968.         4.  Glazing:  Sealed insulating glass unit, 7/8 inch unit
  969.             thickness, with fully-tempered DSB glass.
  970.         5.  Glazing:  Low-e sealed insulating glass unit, 7/8
  971.             inch unit thickness, with fully-tempered DSB glass
  972.             and argon gas fill.
  973.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  974.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  975.             Spacer System.
  976.         7.  Frame:  PVC extrusions, mechanical butt-joint
  977.             construction, stainless steel track; sloped vinyl
  978.             sill for positive drainage.
  979.         8.  Sash:  PVC extrusions, fusion-welded construction,
  980.             mitered corners, steel-reinforced vertical members on
  981.             operable panel, operable sash unit with adjustable
  982.             dual-roller system, full-interlocking meeting rails,
  983.             full sash capture at jamb, and latching hardware with
  984.             keeper.
  985.         9.  Insect screening:  Roll-formed or extruded aluminum
  986.             channel frames, with 18 by 16 fiberglass mesh secured
  987.             with continuous vinyl gasket, removable for screen
  988.             replacement; four-point adjustable rollers.
  989. NOTE ** Delete options specified in the following two sub-
  990.         paragraphs if not required.
  991.         10. Muntins:  Colonial grid installed between outer and
  992.             inner glass panes during fabrication of insulating
  993.             glass units.
  994.         11. Hardware operation:  Keyed lock on exterior side,
  995.             with two (2) keys.
  996. NOTE ** Retain the following paragraph if specifying ALSIDE
  997.         1100 horizontal-sliding patio door units.
  998.  
  999.     C.  Acceptable Product:  ALSIDE MODEL 1100.
  1000.         1.  Grade:  ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
  1001.             72-inch wide by 80-inch high door unit; exceeding
  1002.             grade requirements as follows:
  1003.             a.  Water test pressure:  3.75 pounds per square
  1004.                 foot.
  1005.             b.  Air infiltration: 0.09 cubic feet per minute per
  1006.                 linear foot at 25 miles per hour.
  1007. NOTE ** Delete one of the following two sub-paragraphs;
  1008.         first is for standard glazing, second is for low-e
  1009.         glazing with argon gas fill.  Consult with
  1010.         manufacturer for thermal performance data if
  1011.         optional colonial grooved or tinted glazing is
  1012.         specified.
  1013.         2.  Thermal performance, in accordance with NFRC 100, for
  1014.             72-inch wide by 96-inch high door unit:  U-Value
  1015.             0.49.
  1016.         3.  Thermal performance, in accordance with NFRC 100, for
  1017.             72-inch wide by 96-inch high door unit:  U-Value
  1018.             0.34.
  1019. NOTE ** Delete one of the following two sub-paragraphs to
  1020.         specify glazing type required; first is for
  1021.         standard glazing, second is for low-e glazing with
  1022.         argon gas fill.  Colonial grooved glazing and
  1023.         tinted glazing are options; consult with
  1024.         manufacturer.
  1025.         4.  Glazing:  Sealed insulating glass unit, 7/8 inch unit
  1026.             thickness, with fully-tempered DSB glass.
  1027.         5.  Glazing:  Low-e sealed insulating glass unit, 7/8
  1028.             inch unit thickness, with fully-tempered DSB glass
  1029.             and argon gas fill.
  1030.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  1031.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  1032.             Spacer System.
  1033.         7.  Frame:  PVC extrusions, fusion-welded construction,
  1034.             mitered corners; vinyl sill with aluminum roller
  1035.             track.
  1036.         8.  Sash:  PVC extrusions, fusion-welded construction,
  1037.             mitered corners, steel-reinforced vertical members on
  1038.             operable sash unit with adjustable dual-roller
  1039.             system, full-interlocking meeting rails, full sash
  1040.             capture at jamb, and latching hardware with keeper.
  1041.         9.  Insect screening:  Roll-formed or extruded aluminum
  1042.             channel frames, with 18 by 16 fiberglass mesh secured
  1043.             with continuous vinyl gasket, removable for screen
  1044.             replacement; four-point adjustable rollers.
  1045. NOTE ** Delete options specified in the following two sub-
  1046.         paragraphs if not required.
  1047.         10. Muntins:  Colonial grid installed between outer and
  1048.             inner glass panes during fabrication of insulating
  1049.             glass units.
  1050.         11. Hardware operation:  Keyed lock on exterior side,
  1051.             with two (2) keys.
  1052. NOTE ** Delete the following Article if no casement window
  1053.         units required.
  1054.  
  1055. 2.6 CASEMENT WINDOW UNITS
  1056. NOTE ** Retain the following paragraph if specifying ALSIDE
  1057.         0961 casement window units.
  1058.  
  1059.     A.  Acceptable Product:  ALSIDE MODEL 0961.
  1060.         1.  Grade:  ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
  1061.             26-inch wide by 50-inch high window unit; exceeding
  1062.             grade requirements as follows:
  1063.             a.  Water test pressure:  5.25 pounds per square
  1064.                 foot.
  1065.             b.  Air infiltration:  0.04 cubic feet per minute per
  1066.                 linear foot at 25 miles per hour.
  1067. NOTE ** Delete one of the following two sub-paragraphs;
  1068.         first is for standard glazing, second is for low-e
  1069.         glazing with argon gas fill.  Consult with
  1070.         manufacturer for thermal performance data if
  1071.         optional obscure or tinted glazing is specified.
  1072.         2.  Thermal performance, in accordance with NFRC 100, for
  1073.             30-inch wide by 60-inch high window unit:  U-Value
  1074.             0.44.
  1075.         3.  Thermal performance, in accordance with NFRC 100, for
  1076.             30-inch wide by 60-inch high window unit:  U-Value
  1077.             0.30.
  1078. NOTE ** Delete one of the following two sub-paragraphs to
  1079.         specify glazing type required; first is for
  1080.         standard glazing, second is for low-e glazing with
  1081.         argon gas fill.  Obscure glazing and tinted glazing
  1082.         are options; consult with manufacturer.
  1083.         4.  Glazing:  Sealed insulating glass unit, 13/16 inch
  1084.             unit thickness, with DSB glass.
  1085.         5.  Glazing:  Low-e sealed insulating glass unit, 13/16
  1086.             inch unit thickness, with DSB glass and argon gas
  1087.             fill.
  1088.         6.  Sealed Insulating Glass Units:  Conform to ASTM E
  1089.             774, Level CBA, utilizing PPG Warm-Edge "Intercept"
  1090.             Spacer System.
  1091.         7.  Frame:  PVC extrusions, fusion-welded construction,
  1092.             mitered corners.
  1093.         8.  Sash:  PVC extrusions, fusion-welded construction,
  1094.             mitered corners, operable sash unit with single-
  1095.             handle multi-point locking system, positive-action
  1096.             rotary-crank operator system, with handle.
  1097.         9.  Insect screening:  Roll-formed or extruded aluminum
  1098.             channel frames, with 18 by 16 fiberglass mesh secured
  1099.             with continuous vinyl gasket, removable for screen
  1100.             replacement.
  1101. NOTE ** Delete the following paragraph if muntins are not
  1102.         required.
  1103.         10. Muntins:  Colonial grid installed between outer and
  1104.             inner glass panes during fabrication of insulating
  1105.             glass units.
  1106.  
  1107. 2.7 FABRICATION
  1108.  
  1109.     A.  Window/Door Units:  Assemble units completely in factory,
  1110.         including operating hardware and glazing.
  1111.  
  1112.  
  1113. PART 3  EXECUTION
  1114.  
  1115. 3.1 EXAMINATION
  1116.  
  1117.     A.  Verification of Conditions:  Openings are in correct
  1118.         location, and of correct size, in accordance with
  1119.         approved shop drawings and manufacturer's installation
  1120.         instructions.
  1121.  
  1122.     B.  Installer's Examination:
  1123.         1.  Have installer of this section examine conditions
  1124.             under which construction activities of this section
  1125.             are to be performed, then submit written notification
  1126.             if such conditions are unacceptable.
  1127.         2.  Transmit two copies of installer's report to
  1128.             Architect within 24 hours of receipt.
  1129.         3.  Beginning construction activities of this section
  1130.             before unacceptable conditions have been corrected is
  1131.             prohibited.
  1132.         4.  Beginning construction activities of this section
  1133.             indicates installer's acceptance of conditions.
  1134.  
  1135. 3.2 INSTALLATION
  1136.  
  1137.     A.  Install products specified in this section square, plumb
  1138.         and level, in accordance with approved shop drawings and
  1139.         manufacturer's installation instructions.
  1140.  
  1141.     B.  Installation of joint sealers is specified in Section
  1142.         07900.
  1143.  
  1144. 3.3 ADJUSTING
  1145.  
  1146.     A.  Adjust operating hardware for correct operation in
  1147.         accordance with manufacturer's installation instructions.
  1148.  
  1149. 3.4 CLEANING
  1150.  
  1151.     A.  Clean interior and exterior surfaces free of labels,
  1152.         mortar, plaster, paint, joint sealers, and other foreign
  1153.         matter to prevent damage to weatherstrip, and to prevent
  1154.         interference with operation of hardware.
  1155.  
  1156. 3.5 PROTECTION
  1157.  
  1158.     A.  Protect ventilators and operating parts from dirt and
  1159.         damage caused by subsequent construction activities.
  1160.  
  1161.     B.  Replace units damaged by subsequent construction
  1162.         activities.
  1163.  